Top navigation bar for CareBase power quality website, homepage and product specification pages focused on mission-critical power systems protection, battery backup, precision voltage regulation and redundant on-line UPS using automatic transfer switches.

The latest news and product announcements. Power/surge protection, conditioning, control, battery backup and voltage regulation products. White Papers-Articles On Understanding and Achieving High Availability & High Quality Power Double Conversion True On-Line Battery Backup - Uninterruptible Power Systems & Single Conversion UPS Outdoor UPS for Extreme Temperature/Weather Environmental Conditions In Exterior Rated NEMA Enclosures AC Automatic Transfer Switches For Redundant Power Sources or UPS Bypass AC Power Conditioners - Low-Impedance Isolation Transformer and Ferroresonant Transformers Left navigation bar for the CareBase website focusing on mission-critical power systems and surge protection, utilizing UPS, precision automatic voltage regulators, line conditioners, battery backups, automatic transfer switches, on-line outdoor UPS, surge protective devices and more.
 

CareBase
TM
 

 

Automatic Redundancy Module

enables redundant ac power auto-transfer or is a UPS bypass switch

Click here for complete specifications in 
a printer friendly Adobe Acrobat PDF format

ARm-1000E
230V ac, 10 amperes

TSi Power’s ARm-1000E redundancy module ~ automatic bypass system is recommended when no downtime from power outage is tolerated. Internet service providers, critical servers and telecom equipment, and export markets with bad power would find this technology valuable. The ARm Series permits daisy chaining with synchronous sinewave power sources or UPS.

One major caveat to consider though: Both inputs MUST ALWAYS be in phase. This usually is not the case, so these units are used more for manual UPS bypass switches. For an automatic transfer switch where both power sources can be asynchronous, or out of phase, see the ATs Series.

Typical ARm Series applications
D
esigned for situations where reliability and predictability matter to the enterprise. 
Examples: telecommunications equipment, export markets, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key automatic redundancy module benefits
T
he ARm will provide uninterrupted ac to your load even in the event of UPS failure. ARms your critical equipment against extended power outages and catastrophic system shutdowns caused by accidental circuit breaker trips, UPS overload conditions, weak or old UPS batteries, routine and preventive maintenance of UPS, accidental UPS shut down, loose power cords, or UPS failure. ARm-1000E permits unlimited redundancy using any combination of independent (separate) 230V ac circuits, UPS systems, generator-backed ac circuits, etc.

How ARm automatic transfer switches work
T
he ARm is fed by two ac power sources. When the primary power source detector circuit senses a loss of power on that circuit, a relay immediately switches the load over to the backup power source feed in less than 10 ms. This is fast enough to be invisible to computer switch-mode power supplies.


Key features of the TSi Power automatic redundancy module
Enables redundant UPS, backup generators or other ac power sources to be used for a single load.
LED status indicators

 

Less than a 10ms transfer time
from source A to source B.
Low cost
DB9 communications interface
Audible alarms with enable/disable switch

 

   SPECIFICATIONS ARm-1000E
    Electrical

 

   Capacity in VA (watts) 2300 VA (2300 watts)
     Switching technology Fast operating / releasing relays
    Input
     Nominal voltage 230 volts ac, single phase
     Primary voltage 190 to 260 volts ac
     Backup voltage 190 to 260 volts ac
     Frequency range 50Hz +/-5%
     Over-current protection Both primary and backup are protected by fuses
     Fuse rating 10 amperes
     Typical transfer time Less than 10ms, primary to back-up and back-up to primary
     Input/output wire size 14 AWG recommended
     Ac inputs 6 ft. (1.8m) three-conductor 14 AWG SJT cord w/ IEC 320 plugs
    Output
     Nominal voltage 230 volts ac, single phase
     Load regulation Better than 2% from no load to full load.
     Power efficiency 98% or higher
     Ac receptacles Four IEC 320 output receptacles
     Indicators Green LED for primary ac presence, Yellow LED for backup ac
presence, flashing Red LED for loss of primary or backup ac.
     Audible alarms Buzzer beeps when loss of primary or backup ac occurs.
     Audible alarm switch Audible alarm (buzzer) and alarm enable/disable switch.
     Alarms contacts interface A rear-mounted DB-9 connector sends loss of primary ac
and loss of backup ac. (pins 1 & 5 are used).
    Physical
     Dimensions  254mmW x 203mmD x 76mmH (10"wide x 8"deep x 3.2"high)
     Weight 2.7 kg (6 lbs)
     Rack mount option Front mount kit: for a 19" rack: use # MK-5019A
    Safety
     In phase requirement Primary and back-up ac must always be in phase.
    Environmental
     Ambient temperature 0° to +40°C, 90% relative humidity (non-condensing).
    Warranty
     Warranty 2 year limited warranty, parts and labor.
TSi's ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies. 

ARm Series 230V system architecture 

                    

TSi Power also manufactures custom automatic transfer switches.
For special applications, please call. 