| |
Specifications |
XINv-600-24V |
XINv-900-24V |
| |
Electrical |
|
Capacity in VA (watts) |
600VA (600W) |
900VA (900W) |
| |
Inverter type |
Pulsed-width-modulated
(PWM) with isolation transformer. |
| |
Input |
| |
Nominal voltage |
-24
volts dc
or +24 volts dc |
| |
Operating voltage |
21 to 29 volts dc |
| |
Maximum input current |
35 amperes |
50 amperes |
| |
Dc input connector |
3 screw terminal
blocks for earth ground, (+), (-) dc inputs |
| |
Recommended wire size |
10mm2
(8
AWG) |
15mm2 (6
AWG) |
| |
Output |
| |
Ac output voltage |
115
volts
+/-3% ac (factory settable to 110 vac or 120 vac) |
| |
Frequency stability |
60
Hz +/-0.5% |
| |
Output waveform |
Pure
sine wave. Less than 5% maximum THD for 0 to 100% loads. |
| |
Load compatibility |
All linear and non-linear loads from -0.6
(leading) to +0.6 (lagging) power factor, including new power-factor
corrected switchmode power supplies & older non-power-factor corrected
power supplies. |
| |
Load crest
factor |
Up to 3:1 crest factor loads can be powered
by the inverter. |
| |
Surge current
capability |
Up to 300% surge power is available to power
load equipment
with high starting/stopping surge currents for a few ac
cycles. |
| |
Overload
capability |
1 minute @ 120% overcurrent. |
| |
Power efficiency |
Greater than 85%
under all load and dc input voltage conditions. |
| |
Power on/off switch |
Recessed on/off
rocker style power switch. |
| |
Isolation and grounding |
100%
isolation between input dc and output ac
(isolation transformer included). Metal enclosure is
bonded to dc input terminal block earth ground input. |
| |
Audible noise |
45 dBA
@ 1.5m |
| |
Ac receptacles |
Eight standard NEMA 5-15R female receptacles. |
| |
Status indicators and
communications |
| |
Status Indicators |
Dc input
voltage indicator: 5 green LEDs (20% per each LED).
Ac output current: 5 green LEDs (20% per each LED).
Inverter On: 1 yellow LED illuminates during normal operation.
Overload: 1 red LED illuminates if overload condition exists. |
| |
Communications |
Rear-mounted DB-9 female signal port.
(For DB9, RS-232C serial communications and optional SNMP interface
information, please see this unit's
specifications PDF) |
| |
Physical |
| |
Dimensions |
406mm(16")wide x 381mm(15")high x 89mm(3.5")deep (2U
high) |
| |
Weight |
12 kg(26 lbs) |
18 kg(38 lbs) |
| |
Rack or wall mounting kits
(optional)
23"/24" also available |
For
standard 19" cabinet: use front pair # MK-5019A
For telecom center-mount rack: use center pair # MK-5019F
For wall or floor mount kit: MK5000C |
| |
Safety |
| |
Agency approvals |
Designed
to meet IEC 60950 safety standards. |
| |
Dc breaker |
Protection against shorts or misapplication
of inverter current. |
| |
Low
voltage disconnect |
Inverter turns off automatically if input
voltage drops below 21vdc. |
| |
Overload shutdown |
Inverter turns off automatically if overload
is >120% over 1 minute. |
| |
Environmental |
| |
Ambient temperature |
-20°
to +40°C
(-4° to
+104°F),
5 to 95% relative humidity
(non-condensing). Storage temp. -20°
to +60°C(-4°
to +140°F) |
| |
Cooling Method |
Forced
air (internal hot air exhaust fan is included. |
| |
Elevation |
0 to 4000 meters (0 to 12,400 feet) above
sea level. |
| |
Warranty |
| |
Warranty |
2
year limited depot warranty, parts and labor. |