Top navigation bar for CareBase power quality website, homepage and product specification pages focused on mission-critical power systems protection, battery backup, precision voltage regulation and redundant on-line UPS using automatic transfer switches.

The latest news and product announcements. Power/surge protection, conditioning, control, battery backup and voltage regulation products. White Papers-Articles On Understanding and Achieving High Availability & High Quality Power Double Conversion True On-Line Battery Backup - Uninterruptible Power Systems & Single Conversion UPS Outdoor UPS for Extreme Temperature/Weather Environmental Conditions In Exterior Rated NEMA Enclosures AC Automatic Transfer Switches For Redundant Power Sources or UPS Bypass AC Power Conditioners - Low-Impedance Isolation Transformer and Ferroresonant Transformers Left navigation bar for the CareBase website focusing on mission-critical power systems and surge protection, utilizing UPS, precision automatic voltage regulators, line conditioners, battery backups, automatic transfer switches, on-line outdoor UPS, surge protective devices and more.
 

CareBase
TM
 

 


Isolation Transformer
Line Conditioner


with a low-impedance EI core,
and with a neutral-ground bond
for common-mode noise elimination for sensitive electronics

Isolation transformer line conditioner with neutral-ground bond, low-impedance, EI core, 0.6kVA/600VA,1kVA/1000VA, best all around surge protection.

Click here for complete specifications in 
a printer friendly Adobe Acrobat PDF format
ILc Series
 120 vac, 600VA and 1000VA
TSi Power’s ILc Series line conditioner provides the best all-round power conditioning and surge protection for sensitive electronic equipment. The integral isolation transformer provides 100% isolation from the input ac line ~ the secondary neutral-to-ground bond eliminates all surge voltages between neutral and ground. Surge protection and noise filtering are superior to conventional surge protection and filtering devices.

Typical ILc line conditioner applications
D
esigned for situations where reliability and predictability matter to the enterprise. 
Examples include: point-of-sale terminals, telecommunications equipment, file servers, routers, digital copiers, office machines, industrial controllers (PLC), automatic test equipment (ATE), laboratory analyzers and other sensitive, specialized microprocessor-based equipment.

Key ILc power conditioning benefits
I
Lc Series conditioners reduce the need for a high quality ground and a dedicated line, while eliminating interference from adjacent sources of disturbances. ILc contributes to enhanced operation, improved repeatability, fewer reboots and system lock-ups and extended operating life. 
In addition, a reduction in equipment down time and service costs can be expected.

How ILc line conditioners work
T
he integral isolation transformer provides complete isolation between the primary and secondary, and permits bonding its output neutral to ground, which completely eliminates all disturbances between neutral and ground, regardless of source. The series inductance of the isolation transformer in combination with a capacitive element and an MOV, provide superb noise filtering, as well as coordinated multi-stage surge protection in accordance with the principles of IEC 61312.3.


Key features of the TSi Power isolation power conditioner

Coordinated surge protection
Per IEC 61312.3

Low-impedance 
isolation transformer

True isolation

Common-mode noise elimination

High efficiency

 

Advanced noise and interference
Filter reduces dV/dt from
6kV/µs to less than 10V/µs

Four ac outlets

Quiet operation

Low weight

Five year warranty

 

   SPECIFICATIONS ILc-600B ILc-1000B
    Electrical

 

   Capacity in VA (watts) 600 VA (600 watts) 1000 VA (1000 watts)
     Transformer type Low-impedance E-I core isolation transformer
    Input
     Nominal voltage 120 volts ac, single phase
     Operating voltage 100 - 130 volts ac
     Nominal frequency  60 Hz +/-3
     Over-current protection User resettable circuit breaker built-in
     Circuit breaker rating 5 amperes 10 amperes
     Ac input cord 6 foot long ac power cord with NEMA 5-15P plug
    Output
     Nominal voltage 120 volts ac, single phase
     Power efficiency 94% (typical)
     Total harmonic distortion < 1%
     Surge protection A three stage surge protection system consisting of 
isolation transformer, capacitor and MOV is included.
     Surge test conditions Per ANSI/IEEE C62.41-1991 test waveforms.
     Surge let-through voltages Single pulse: L-N: 50V, L-G: 50V, N-G: 0.5V
Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V
The measured rate of voltage rise/fall (dV/dt of the remnant waveform 
is less than 10V/
ms with input test waveform dV/dt of 6kV/ms.
     Ac receptacles Four (NEMA 5-15R)
    Physical
     Dimensions 152mm(6")wide x 127mm(5")high x 229mm(9")deep
     Weight 11.3 kg (25 lbs) 15 kg (33 lbs)
    Safety
     Agency approvals UL and cUL Listed
    Environmental
     Ambient temperature 0° to +40°C (32° to +104°F), 90% relative humidity (non-condensing).
    Warranty
     Warranty Five year limited warranty, parts and labor
TSi's ongoing product improvement process makes specifications subject to change. Other companies product names herein are for identification purposes only, and may be trademarks of their respective companies. 

ILc-1000B rear view (shown without line cord/plug)

Rear view, isolation transformer line conditioner with neutral-ground bond, low-impedance, EI core, 0.6kVA/600VA,1kVA/1000VA, best all around surge protection, 120V/120vac.

ILc series system architecture

System architecture drawing, 1kVA, 1000W, 120V/120vac isolation transformer with neutral-ground bond, surge protection, noise filter.

TSi Power also manufactures custom (bespoke) power conditioners.
For special applications, please call. 

Back to top

 

                                               CareBase ~ PO Box 2987 ~ Glenwood Springs, Colorado  81602-2987 ~ USA ~ +1 970 945 2770 ~ 800.430.2770 (USA/CAN)
                                                   Please e-mail michael.gibson@carebase.com re: questions, RFQs, applications, etc. Copyright 1988- 2006 CareBase
                                                                                                                                  Hit Counter